level 3 colocation

adapt's London City facility is based at the London Gateway of leading network provider Level 3 Communications. This facility provides direct connectivity to the World's largest IP backbone; for the best performing and lowest latency bandwidth.

Colocating your servers and services within a Level 3 data centre has the unique advantage of being on-net to a large percentage of the financial community and content and media providers.

  • London City Tier lll data centre
  • Tier 1 IP backbone
  • Financial community - on-net
  • Ideal for low latency bandwidth
  • Vyvx Hub
  • Key node for access to Level 3 CDN networks

adapt have been in partnership with Level 3 for over 10 years and are Level 3's European Premier Master Reseller.

Benefits

  • Integrated with adapt's UK data centres
  • Directly connected to Level 3 IP backbone
  • On-net to global financial community, major content and media players
  • Access to content delivery networks (CDN)
  • Various transport offerings
  • Flexible power solutions
  • kW commercial models
  • Carrier neutral facility
  • Rapid deployment of custom build private suites
  • Managed data centre infrastructure
  • Flexible contract terms
  • Intelligent integrated active server enclosures
  • Environmental sensors included as standard
  • Secure local and remote cabinet access
  • Ideal for split site solutions and Synchronous Replication
  • High Availability services

Mains Power

  • Dual redundant 20MVA, 33kV dedicated underground mains feeds
  • 5 x 3.8MVA 11kV diesel driven emergency power generators.
  • Automatic start in less then 1 Minute to feed 100% of the facility
  • Fuel storage for 24hour continuous operation at 100% load

UPS

  • 3 separate systems of 5 x 625kVA hybrid rotary UPS modules providing 2500kVA output each with N+1 redundancy
  • Total facility UPS capacity 7500kVA N+1
  • 15 Minute battery autonomy per UPS module
  • Dual redundant A & B distribution

DC

  • 8000Amps -48VDC power system for telecom network equipment
  • 4 Hour battery autonomy
  • Dual bus systems with dual redundant A & B distribution


Environment

  • Cooling criteria: 750W/m², 21°C +/- 2°C, 50%RH +/- 10%
  • Under floor cooling air distribution
  • N+1 Perimeter down flow chiller water cooling units
  • 13x1100kWr air cooled package chillers giving 12,100kWr with N+2 redundancy

Physical

  • Minimum floor to ceiling clearance: 2,570mm from top of raised floor
  • 350mm-550mm raised floor height
  • Raised floor loading 14kN/m²
  • Structural floor slab 5kN/m²

Fire Strategy

  • Very intelligent early warning (VIEW) detection - above and below raised floor
  • Smoke extract system at 12 air changes per hour
  • Double interlocked pre-action dry pipe sprinkler system

Security

  • Full electronic access control system, based on proximity cards, PIN keypads and biometric palm-scanners for colocate rooms
  • Intruder detection system on escape and riser doors
  • CCTV monitoring and recording of all access points and circulation areas


Building Monitoring System (BMS)

  • 24x7 local monitoring and logging of environment alarms and conditions
  • Critical alarm repeating to London RMC
  • Full perimeter under floor leak detection linked to building monitoring system

Telecoms Infrastructure

  • Facility is designed to accommodate standard rack/cabinets of 2,200mm nominal height
  • Power distributed under floor, fibre and copper cabling distributed overhead (fibre within a managed containment system, copper within a heavy duty racking system)
  • The building has two fibre access points
  • Carrier connectivity: Level 3, COLT, BT,C&W, Interoute, Tiscali/NETS, 51 degrees,THUS and adapt

General Facilities

  • Dedicated loading area
  • Customer test room and storage area
  • 2 goods lifts (maximum loads - 3,950kg & 4,400kg)

020 3009 3300 or email to find out more about adapt and Level 3 or watch the level 3 data centre video